Feel Free to Call us on 01296 841007 To Discuss Your Drainage Requirements



Marsh Effluent Single Pump Station - 561L

Marsh Industries

Regular price £1,025.00

Designed for use in combination with a package sewage treatment plant, this single pump station operates by gathering wastewater and pumping it at high pressure to the sewer system, after which natural gravity takes over. The station's single free-standing design makes it easy to install and maintain, ensuring reliable operation.

Level control devices such as a float switch or liquid level sensor monitor the wastewater as it enters the pump station chamber from the sewage treatment plant. When triggered, the pump uses high pressure to lift the wastewater through a system of discharge pipes into the public sewer. As a single pump station, it is suitable for ensuring maximum efficiency and reliability in transferring wastewater from outbuildings with a toilet or home extension to the public sewer system.

Features & Benefits: Marsh Effluent Single Pump Station Free-standing - 600 x 2000mm

  • Single pump station designed for use with a package sewage treatment plant
  • Pumps wastewater at high pressure to the sewer system
  • Single free-standing design for easy installation and maintenance
  • Level control devices monitor wastewater as it enters the pump station chamber
  • High pressure pump ensures maximum efficiency and reliability
  • Suitable for outbuildings with a toilet or home extension
  • Available in different sizes
  • All stations have 32mm outlet connection and a 500m inlet invert

Available in a variety of sizes to suit your site's requirements, each station has a 32mm outlet connection and a 500m inlet invert.

    Each pump chamber contains a number of float switches linked to a control panel that automatically controls flow and levels.

    In a single pump chamber there are three float switches:
    Float A: Actuates the pump cycle until level drops to low level.
    Float B: Low level float stops the pump.
    Float C: High level alarm – positioned above the pump actuator float (min 100mm).

    For twin pump chamber operation there is an additional float switch (Float D) – usually positioned 150mm above first actuator (A) – which actuates the second pump in periods of higher flow.

    After each cycle the pumps alternate to extend pump life and are designed to run for a minimum of 60 seconds with no more than 15 starts per hour.

    Model Diameter
    +/-50mm
    Height
    +/-50mm
    Inlet invert Inlet dia Outlet invert Outlet dia Storage below invert Total storage
    Mini 600 1100 500 110 300 32 120 234L
    Midi 600 1500 500 110 300 32 280 421L
    Maxi 600 2000 500 110 300 32 421 561L
    CPS1 1170 1100 500 110 300 32 470 867L
    CPS2 1170 1500 700 110 300 32
    780 1183L
    CPS3 1170 2200 900 110 300 32 1025 1735L
    CPS4 1170 2600 900 110 300 32 1340 2050L
    CPS5 1958 2100 900 110 300 32 2440 3700L
    CPS6 1958 3400 900 110 300 32
    4000 6000L
    • Free delivery to UK Mainland sites (Scottish Highlands excl., please contact us for a delivery prices).
    • Offloading is the Customers responsibility 
    • Delivery dates are subject to change with respect to product availability